Mode:FS-ETH-SC09 For FX series PLC Ethernet adapter
Version Info
Document name:USER MANUAL Of FS-ETH-SC09
Version:V2.0
Revising Date: September 26,2010
Relevant Documents
In order to use the FS-ETH-SC09 better, you also need to read the following documents:
1.Device Manager Parameters setting software manual
2. VCOMM virtual Serial Port software ManualContent
1.FS-ETH-SC09 1PC
2. RJ45 Cable 1 PC,2 M
3.CD 1PC
(1) Characteristics & Technical Parameters
FX Series PLC refers to FX0/FX0S/FX0N/FX1N/FX2N/FX3U/FX3G ... .... .
Notice:when the FS-ETH-SC09 is used to communicate between the PC and the FX series PLC or between PLC and PLC, it supports the RS422/RS485/RS232 communication which meet UART serial data communication standard. Some field buses such as PROFIBUS, PPI, MPI, CC-Link, PC-Link, etc., although the physical interface is RS485, they do not comply with the UART serial data format, so they do not apply to this product!
*High-speed, highly reliable industrial-grade standard, anti-interference design for harsh electromagnetic environment
* 32 bit RISC (NP7 series) ARM7TDMI 55DMIPS
* 128KB SRAM,128KB Code + 32KB Boot
*10M/100M adaptive Ethernet interface
* Support RS422/RS485 data bits 5,6,7,8 settable
* Support RS422/RS485 stop bit 1,1.5,2 settable* Support RS422/RS485 parity NONE, ODD, EVEN, MARK, SPACE settable*Support RS422/RS485 baud rate 110 ~ 115200bps standard rate settable *Support the RS422/RS485 communications which meet UART serial data communication standard, do not support field bus protocol.*Smart protocols: TCP, UDP, ARP, IP, ICMP, DHCP, BOOTP, DNS
*Support dynamic DNS *Working mode can be TCP Server, TCP Client, UDP multicast and unicast UDP *Built-in Flash memory, can save the setted parameters* Support Windows 95/98/ME/NT/2000/XP/2003/XP/Win7 operating system, Vista is not recommended * RJ45 port 1500VDC electromagnetic isolated,RS422 interface 1500VDC electromagnetic isolated,* Interface protection: power supply port has the reverse polarity protection and over current protection, RS422 interface has the surge protection ;all pins and terminals have anti-static protection.* 5V±10% DC power supply from FX series PLC RS422 socket,1W power
* Dimension: L × W × H = 65mm × 51mm × 26mm, 35mm Standard rail mounting * Operating Temperature: -40 ° C to +80 ° C (-40 ° F to 176 ° F), 5% to 95% RH (industrial grade) * Storage Temperature: -40 ° C to +80 ° C (-40 ° F to 176 ° F), 5% to 95% RH
(2)External structure &pin definition
Ethernet interface: Standard RJ45 socket, automatically adapt 10M/1000M Ethernet .Use the standard network cable, not crossover cable whether you connect the switch or directly connect to the PC.
The network status LED indicator on the RJ45 socket
LINK LED (left, green) | ACT LED (right, yellow) | ||
condition | description | condition | description |
Regular light | Network cable is connected correctly, work properly. | flash | Sending and receiving data through the RJ45 port |
flash | Network cable is not plugged in, no available network. | extinguish | No data transceiving |
Ethernet interface RJ45 socket signal definition
Pin | Signal Name | Function | Type |
1 | Tx+ | Positive phase differential signal line of Ethernet data sending | output |
2 | Tx- | negative phase differential signal line of Ethernet data sending | output |
3 | Rx+ | Positive phase differential signal line of Ethernet data receiving | input |
4 | Not used | - | |
5 | Not used | - | |
6 | Rx- | negative phase differential signal line of Ethernet data receiving | input |
7 | Not used | - | |
8 | Not used | - |
RS422 communication indicator: there are three LED lights on the panel and its working state as follows:
Indicator | Regular light | Flash | Extinguish |
PWR(Red) | normal | Error | Error or no power supply |
TxD (yellow) | Error or reversal signal polarity | Serial port is receiving the data | Error or no communication |
RxD (green) | Error or reversal signal polarity | Serial port is sending the data | Error or no communication |
(3)Inner diagram
Owing to space is limited, please login the company's official website read.
(4)The parameters set of FS-ETH-SC09
FS-ETH-SC09 needs to be configured the parameters to work correctly, the configuration parameters including the network parameters, communication protocols, connection, serial port parameters;
(5)GX Developer software setting
Click the main menu "Online \ Transfer Settings" to set the COM port = FS-ETH-SC09 simulated COM port in the VCOMM virtual serial port software , the transmission speed = 9.6Kbps. Then you can use as the traditional SC-09 programming cable, and you can upload, download and compare the program data
(6)The usage in the LAN
The FS-ETH-SC09 communication in the LAN needs to ensure that PC, FS-ETH-SC09 and routers have the same gateway, The gateway: 192.168.1.1, the computer IP address: 192.168.1.108, FS-ETH-SC09 IP address: 192.168.1.250 in the following examples.
1. The communication between the PC and a FX in the LAN
Owing to space is limited, please login the company's official website read.
Of course you can use FS-ETH-SC09 to simulate each PLC as a COM port on the PC in order to achieve the data communication and monitoring operation between PC and multiple PLC s
(2)The communication among the PC and multiple FXs
There is a kind interface board with wide range of applications in Mitsubishi FX series PLC : FX1N-485-BD, FX2N-485-BD, FX3U-485-BD, FX3G-485-BD, all is called as FXxx-485-BD.
Owing to space is limited, please login the company's official website read.(3)The intercommunication among the multiple FXs
FS-ETH-SC09 in the picture need to go through the connection between FXxx-422-BD interface board and the FX series PLC, mainly to facilitate the installation of FS-ETH-SC09, in fact it’s the same as the usage of FXxx-485-BD.
Owing to space is limited, please login the company's official website read.
(7) Remote communication in the internet
FS-ETH-SC09 can achieve the worldwide remote communication through the Internet, it will use the external network IP address of the router, the router external network address is different when the router is started every time, because the router will be randomly assigned to one IP address from the Internet when it ‘s powered every time, so this will result in trouble for remote communication through the Internet,
Owing to space is limited, please login the company's official website read.(8) Remote wireless communication in the 3G wireless internet
Owing to space is limited, please login the company's official website read.(10)Appendix: the basic knowledge of the Ethernet